Lucene search

K

MicroSCADA X SYS600 Security Vulnerabilities

cve
cve

CVE-2022-3353

A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products. An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client...

7.5CVSS

7.3AI Score

0.004EPSS

2023-02-21 02:15 PM
23
cve
cve

CVE-2022-3388

An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's...

7.8CVSS

7.8AI Score

0.001EPSS

2022-11-21 07:15 PM
34
2
cve
cve

CVE-2022-29492

Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a...

7.5CVSS

7.5AI Score

0.001EPSS

2022-09-14 06:15 PM
36
2
cve
cve

CVE-2022-2277

Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP.....

7.5CVSS

7.6AI Score

0.001EPSS

2022-09-14 06:15 PM
24
4
cve
cve

CVE-2022-1778

Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy...

4.4CVSS

5.8AI Score

0.0004EPSS

2022-09-14 06:15 PM
28
4
cve
cve

CVE-2022-29922

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the...

7.5CVSS

7.5AI Score

0.001EPSS

2022-09-14 06:15 PM
30
6
cve
cve

CVE-2022-29490

Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to....

8.8CVSS

8.7AI Score

0.001EPSS

2022-09-12 09:15 PM
32
2